Free tool

Camper or RV solar panel wiring calculator

Planning solar for a camper van, RV or skoolie? This free calculator shows how to wire your solar panels (in series, in parallel or both) and what size charge controller you need. It checks your array against Victron SmartSolar MPPT limits, including cold-weather voltage, then draws a wiring diagram with the fuses, disconnect breaker and parts to buy.

Enter your panel specs or pick a preset, then choose how many panels go in series and parallel. The voltage, current and charge controller update as you go. Not sure which to pick? Read series vs parallel for camper van solar.

Your panel

Panel specs

Voc is open-circuit voltage; Isc is short-circuit current.

Optional

The Voc coefficient from the sticker.

Decides whether parallel strings need fuses.

Numbers are on the sticker on the back of the panel. Presets can differ between panel revisions, so check yours.

Your system

Battery voltage

The coldest morning the panels will see. Cold raises panel voltage.

Charge controller

Smallest Victron that fits

Victron SmartSolar MPPT 100/30

Takes up to 100 V and 35 A from the panels, and is rated for about 435 W at 12 V. Enough for all 400 W of your array.

See the 100/30 on Amazon

Some links are affiliate links. I earn from qualifying purchases, at no extra cost to you.

Another brand? Look for at least 49 V max PV voltage, 12 A max PV short-circuit current, and 28 A of charge current at 12 V.

Parts you’ll need

Some links are affiliate links. I earn from qualifying purchases, at no extra cost to you.

Fuses and breakers use the common 1.56 × Isc rule on the array side and 1.25 × the controller’s rating on the battery side.

Your array

How they’re wired

Per string. Adds voltage.

Adds current.

2 panels total

Roof200W200WRoof glandDisconnect20 A breakerBus bars40 A fuse+−12 V batteryMPPTBATTERYPV+−−+

Use the wire sizing tool below to work out the wire gauges you need.

2 in series × 1 in parallel (2s1p), 2 panels

Array power
400 W
Voltage at 14 °F / −10 °C
48 V43.6 V at 77 °F
Short-circuit current
11.6 A
Charge current at 12 V
≈ 27.6 AFull sun

Requirements

Inline MC4 fuses
Not neededA single string has nothing to feed back into it.

What size wires do you need?

Blank uses 15 A from your design.

Enter the length to see the wire size.

Open the full wire size calculator

Check each stretch separately. They carry different currents over different lengths:

  • Panels to the controller. From the panels, through the roof gland and the disconnect, to the controller.
  • Controller to the battery. Carries the controller’s full charge current at 12 V, so it’s usually the thickest of the three.

How it works

  • Series adds voltage and keeps current the same. Parallel adds current and keeps voltage the same. Higher voltage means lower current, which means thinner wire from the roof.
  • Cold voltage: panel voltage rises as temperature falls. The tool raises Voc from 77 °F (25 °C) down to your coldest temperature using the panel's temperature coefficient. That number must stay under the controller's maximum PV voltage, or the controller can be damaged.
  • Short-circuit current: the array's total Isc has to stay under the controller's maximum PV short-circuit rating. This is what limits how many strings you can put in parallel.
  • Power: a controller caps its output at its rated charge current. A somewhat bigger array still works; the extra watts just go unused in full sun. The tool shows the smallest SmartSolar that passes the whole array.
  • Mixed panels: panels in series share one current, so the weakest one holds the rest back. Strings in parallel share one voltage, so strings with different voltages each give up a little. The mixed tab estimates that loss. It's a model, not a measurement.

Limits

  • Always confirm the controller's limits against Victron's current datasheet for the exact model before buying.
  • Fuse and breaker sizes use common rules of thumb. Check them against the code that applies to your install and the panel and controller manuals.
  • This is a starting point for planning, not a substitute for the panel and controller manuals.

Example wiring diagrams

Common van setups, drawn by the calculator.