DC wire size calculator
Enter the load, the run length and how much voltage drop you can live with. You get the smallest wire that passes both the voltage drop check and the ampacity check, plus a chart for quick lookups. Based on the ABYC E-11 method that marine and RV wire charts use.
Wire size
4 AWGminimum
Limited by voltage drop (10 AWG would carry the current, but it drops too much voltage over this length).
- Voltage drop
- 0.26 V (2.1%)
- Power lost in the wire
- 12.9 W
- Wire rating here
- 160 A
| Amps ↓ / one-way ft → | 2 | 5 | 10 | 15 | 20 | 25 | 30 |
|---|---|---|---|---|---|---|---|
| 5 A | 16 | 16 | 14 | 12 | 12 | 10 | 10 |
| 10 A | 16 | 14 | 12 | 10 | 8 | 8 | 6 |
| 15 A | 16 | 12 | 10 | 8 | 6 | 6 | 4 |
| 20 A | 16 | 12 | 8 | 6 | 6 | 4 | 4 |
| 30 A | 14 | 10 | 6 | 4 | 4 | 2 | 2 |
| 40 A | 12 | 8 | 6 | 4 | 2 | 2 | 1 |
| 50 A | 10 | 8 | 4 | 2 | 2 | 1 | 1/0 |
| 75 A | 8 | 6 | 2 | 1 | 1/0 | 2/0 | 3/0 |
| 100 A | 6 | 4 | 2 | 1/0 | 2/0 | 3/0 | 4/0 |
| 150 A | 4 | 2 | 1/0 | 3/0 | 4/0 | – | – |
| 200 A | 2 | 2 | 2/0 | 4/0 | – | – | – |
| 300 A | 2/0 | 2/0 | 4/0 | – | – | – | – |
| 400 A | 4/0 | 4/0 | – | – | – | – | – |
Same inputs as above (voltage, drop and temperature). Chart cells use the load current as the fuse rating. A dash means even 4/0 isn’t enough.
How it works
- Voltage drop: required circular mils = 10.75 × amps × round-trip feet ÷ allowed volts lost. The 10.75 is the resistivity of stranded tinned copper.
- Ampacity: the wire has to carry the fuse rating (or the load, if unfused). Ratings are ABYC E-11 values for 105 °C insulation, cut back in hot spaces.
- The bigger of the two wins. Short, high-current runs are usually limited by ampacity; long runs by voltage drop.
Limits
- Use 3% for charging, electronics and anything sensitive. 10% is for loads that tolerate a lower voltage.
- Check that your wire’s insulation is rated 105 °C. Cheaper 80 °C or 90 °C wire has a lower rating.
- Wire size is only half the job: fuse close to the source, and size the fuse to protect the wire.
- This is a starting point, not a substitute for the wire manufacturer’s ratings or the code that applies to you.